JHZZ-100 GIS SF6 Gas Critical Monitoring System
  • JHZZ-100 GIS SF6 Gas Critical Monitoring System

JHZZ-100 GIS SF6 Gas Critical Monitoring System

 
recommendation index:
Mobile SF6 Critical Monitoring System
Real-time detection, timing detection
All-round monitoring of GIS operation status
With historical data query function
  • Mobile SF6 critical monitoring system realizes simultaneous detection of SF6 decomposition, purity and moisture

  • Equipped with fast remote access technology, SMS and email reminders, accurate defect diagnosis results, and a unique critical care expert diagnosis system

  • Real-time detection, timing detection, periodic detection, and critical monitoring density detection functions for suspicious gas chambers

name

component

parameter

minimum detectable quantity

SO2+SOF2、H2S、HF

≤0.1µL/L

large-scale SO2

≤1µL/L

CO,CF4,H2

≤0.5µL/L

purity

≤0.03%

pressure

≤0.001Mpa

dew point

0.1 ℃ 0.1µL / L

temperature

0.1℃

precision

SO2+SOF2、H2S、HF

measured value  ≤ 10 µL/L,  error≤ ± 0.5 µL/L

measured value > 10 µL/L, error ± 5%.

large-scale SO2

detection value> 100 µL/L,  error ≤± 5%.

CO,CF4,H2

measured value ≤ 50 µL/L, error ≤ ± 2.0 µL/L

measured value > 50 µL/L, error  ≤ ± 4%

purity

From 90% to 100%,  error0.20% (m/m).

pressure

0.001

dew point

When the dew point is -60~ 0 ° C, the error is ≤ ± 1.0 ° C

temperature

±0.1℃



Related recommendations

JHZX-SP10 Transformer chromatography online monitoring device

With 7 components of dissolved gas in oil and micro-water monitoring function

JHZX-GP20 type, transformer oil spectrum online monitoring device

Automatic quantitative cycle cleaning, oil intake, oil and gas separation, sample analysis

Add wechat

Scan and add customer service wechat